|
Posted on: 08/08/2000
Improving hvac system performance
by Charles Fafard
Heating, ventilating, and air
conditioning systems consume between 40 and 60 percent of the total energy in most
commercial buildings.
Building management personnel are
interested in improving the performance of these systems, not only to save energy cost,
but also to improve tenant comfort. Therefore, lowering the energy consumption of building
systems should not be the only consideration when evaluating HVAC systems.
HVAC systems can take many forms,
since they comprise all the heating, ventilating, and air conditioning systems within a
building. These systems usually include an air-handling unit with integral heating and
cooling coils. Normally, this unit will be connected to an outside air duct so that the
unit provides ventilation as well as circulation of air within the space.
The first step in improving HVAC
system performance is to evaluate the existing equipment to determine how well it meets
its intended objectives. Questions to ask at this stage include: Does the unit lack
adequate heating and/or cooling capacity? Is sufficient air moved, or is the air stuffy?
If the answer to either of these questions is yes, then the overall system is a candidate
for upgrade or replacement. If the systems meet the basic needs of the space and the
occupants, then system performance and improving energy efficiency should become the
focus.
There are two general guidelines to
consider when evaluating the energy performance of HVAC systems: making the existing
system as efficient as possible and controlling the existing system as efficiently as
possible.
These
principles are based on the fact that HVAC systems are expensive and may not be
cost-effective to replace on the basis of improved performance or estimated annual energy
savings alone. For this reason, most systems are replaced or upgraded when they have
reached the end of their useful life. At that time, various systems can be considered,
including those which are more efficient than existing systems. |
Inspection & Maintenance
One of the first steps is to inspect the
HVAC system at least annually. The entire system should be inspected to determine if
everything is working properly, and that all dampers and linkages are still connected and
opening and closing as designed. All motors should be inspected, and all belts checked to
determine that they are tight. Broken or damaged equipment should be replaced. Once a
general inspection has been accomplished, all equipment should be cleaned and serviced.
Filters should be replaced, dampers adjusted to ensure a tight seal, and linkages cleaned
so that they move freely. Coils should be cleaned to remove all dirt and lint. One study demonstrated the effect of cleaning
coils on HVAC performance, showing that coils that were left uncleaned had a 27 percent
loss in heat transfer after being in operation for 18 months. Even cleaned coils showed a
9 percent loss in heat transfer compared to new coils. Air conditioning systems should
have their refrigerant levels checked and topped off if necessary. Steam traps should be
inspected, and rebuilt or replaced if they leak. Hydronic systems should be bled to
eliminate air pockets that may have accumulated, and water treatment should be verified.
Most of these are routine maintenance
items. However, control systems-especially digital control systems-should be maintained,
calibrated, and serviced at least once a year by a controls company that is familiar with
the type of controls installed in the building. All controls should be sequenced to ensure
proper operation, including verifying proper lubrication and refrigerant charges in air
conditioning equipment. If pneumatic controls are used, the pneumatic lines should be
inspected to correct any leaks. Annual controls maintenance is estimated to cost about
5-10 percent of the original equipment cost.
An annual maintenance program should
include tune-ups, or tuning of fuel-fired equipment. Combustion efficiency tests should be
conducted, and burners adjusted to provide maximum efficiency while minimizing
noncombustibles and excess air. In most cases, 5-9 percent fuel consumption savings are
not unusual after tune-ups.
Boilers
should have their heat transfer surfaces cleaned of scale and soot. A .03125-inch buildup
of soot can reduce energy efficiency by 3 percent. When conducting annual maintenance,
equipment manufacturers' operating instructions should be consulted. If operating
instructions are not available, the manufacturer or vendor should be contacted to obtain
recommended guidelines for routine maintenance. Failure to follow the manufacturer's
recommendations may damage the equipment or cause the warranty to be canceled. |
Efficiency Improvements
In addition to routine inspection and
maintenance, numerous other improvements can be made without spending a lot of money. To
illustrate this, a typical indoor air-handling unit with ductwork will be used. The
following comments refer to various components of this system. Several of these comments
refer to controls that allow the air-handling unit to operate more efficiently. Dampers: The outside air and the exhaust
dampers should be tight-sealing, insulated dampers. Ideally, these should be low-leakage
dampers that limit airflow losses to 5 percent or less; airflow leakage of common dampers
is in excess of 10 percent. The dampers also should have edge and jamb seals that act like
weatherstripping on doors or windows. The damper between the return air duct and the
outside air duct does not need to be insulated, but should be tight-sealing.
The outside-air and exhaust-duct
dampers should be located as close to the outside wall as possible, to minimize the length
of ductwork open to the outside. Even when the ductwork is insulated, heat is still
transferred between the room and the ductwork.
Duct Insulation: Ductwork that
is exposed to outside air-including the mixed air duct, exhaust duct, and outside air
duct-should be insulated to minimize heat loss from the room to the duct. Supply ductwork
also should be insulated, since condensation may occur in air conditioned systems.
Seal Duct Joints: Duct joints
should be sealed with silicone or duct tape, since leakage can account for at least 10
percent of the supply air that escapes.
Air Balance: Air-handling
systems are mechanical devices that are subject to change during their operation. Just as
a car needs to be tuned up, air-handling systems should also be balanced so that excess
air is not being introduced into the building or circulated. A 5 percent savings in cubic
feet of air per minute (cfm) being circulated results in a 14 percent savings in fan
horsepower (see November 1996 Training Series article on piping and ducting systems for
more details).
Ventilation Control: Outside
air is used to provide ventilation for occupants and to offset air exhausted from toilets,
kitchens, and the like. Since most buildings do not operate continuously, outside air is
not needed during unoccupied periods. Heating and cooling of outside air prior to its
delivery to occupied spaces can be very expensive and therefore should be controlled to
match the occupied hours of the building. Energy requirements vary throughout the country,
but heating each cfm of outside air can require up to 100 Btu per hour, while cooling each
cfm can require up to 50 Btu per hour. Since most systems handle hundreds of cfm of
outside air, heating or cooling outside air can be very expensive.
Setback Control: During
occupied periods, buildings are intended to be heated and cooled to provide comfortable
conditions to employees and customers. For example, during unoccupied periods, the heating
temperature can be reduced by 10-15 degrees F. Savings from this control strategy are
normally estimated at 1 percent per degree of setback. The temperature must be returned to
the normal setting for the next occupied period.
Optimum Start: Following a
setback control strategy, many systems are controlled by a time clock or an energy
management system to begin their regular operation. Since building operators need to have
the temperature back to normal conditions when employees arrive, this time setting is
usually conservative so that the heating or cooling begins earlier than actually needed.
An optimal-start strategy utilizes a database and outside temperature measurements to
determine when the system should resume heating or cooling. This allows the system to
remain in setback until the last possible moment, maximizing the savings from the setback
controls.
Occupied/Unoccupied Control:
During occupied periods, most HVAC systems are required to provide continuous air
movement. However, during unoccupied periods, continuous air movement is not necessary.
Therefore, one common technique is to have the air-handling unit cycle during unoccupied
periods to maintain temperature. This saves fan energy, since the fan does not have to run
continuously.
Hot
Water Reset: In hydronic systems, reset controls allow the boiler water temperature to
be reset as the outdoor temperature moderates. This saves energy by not heating the water
higher than needed to heat the building, and also allows better temperature control of the
system. |
System Improvements
More extensive system improvements can be
considered, but these are more expensive. As mentioned earlier, annual energy savings
alone are usually not enough to justify making large-scale changes to HVAC systems.
However, if the system is being replaced because of age or condition, then it is time to
consider systems that provide greater energy efficiency. Here are some upgrade ideas: Economizer: High internal heat gains
often require air conditioning systems to operate even during periods of mild weather. An
economizer system uses large quantities of outside air to meet the cooling load rather
than operating the mechanical cooling system. This involves providing additional controls
to evaluate outside versus indoor air (some systems only measure temperature while others
also measure humidity conditions), ductwork to allow up to 100 percent outside air to be
brought into the building, and an exhaust or relief fan. Certain areas such as computer
rooms should not be considered for economizers because of their special environmental
requirements.
Variable Air Volume: This
system was designed to be constant-volume. Constant-volume systems always deliver the same
quantity of air, and air temperature is changed to control room conditions. Therefore, all
spaces receive the same conditions, even rooms that are not occupied. A variable air
volume (VAV) system maintains a constant supply air temperature and varies the amount of
air delivered to each space. Therefore, spaces requiring less cooling receive less
airflow, while those requiring more cooling receive greater airflow. VAV systems save
energy because it is unusual for all spaces to require full cooling at the same time.
Heat Recovery: Heat recovery is
a general term relating to the useful application of heat that normally would be wasted or
exhausted from a building. Heat recovery is often cost-effective in industrial facilities,
but is not usually cost-effective in commercial buildings because of the low temperature
and small quantity of exhaust from them. One exception is commercial kitchens or
restaurants, where exhaust from the kitchen can often be used for heat recovery. For heat
recovery to be successful, three requirements must be satisfied: a heat source; a heat
target, or use for the heat; and for these two requirements to occur at the same time.
Thermal Storage: Most managers
are more interested in conserving money than in conserving energy. Thermal storage systems
save money in the form of monthly operating expenses. Thermal storage systems are
ice-making systems that are employed at night to produce ice that can then be melted
during the day to provide a chilled-water source for air conditioning.
However, in some cases thermal storage
systems actually use more energy than conventional systems, since making ice is more
energy-intensive than producing chilled water. However, since the system operates at night
during off-peak periods, this strategy can be less expensive if it is coupled with a lower
off-peak power rate.
Part-Load
Boilers and Chillers: HVAC
systems are selected to meet the building's heat loss and gain during design weather
conditions, or the coldest and hottest times of the year. For this reason, individual
boilers and chillers tend to be oversized for most of their operating times. In order to
better track changes in the weather, many engineers are now designing systems with
multiple boilers and chillers. One unit can be sized for 75-80 percent of the design load,
while another is sized for part-load performance, or roughly 30-40 percent of the full
load. This allows the operator to select which unit to operate based on energy-efficiency
performance. When the weather requires full capacity, both units operate; during spring
and fall, only the smaller unit operates. In addition, some systems also use the boiler to
provide domestic hot water. Building operators can install and operate a summer boiler
where previously they had to operate a large boiler during the summer just to produce
domestic hot water. |
Energy Management
Regardless of what improvements are made,
none of these changes should be considered permanent, one-time improvements. HVAC systems
need to be monitored at a minimum of once a year, and then adjusted as required. Even
system replacements are not permanent, since all systems need to be inspected and
maintained. One of the best ways to do this is to establish an energy management program
with systematic checks made of various energy-using equipment. Since most equipment is not
separately metered, monthly energy bills may be the only method available for making
simple checks on energy consumption. Monthly energy use for all fuels should be
plotted using separate graphs for each primary energy source, so that trends can be
observed from year to year.
Weather-dependent systems, such as
HVAC, should be separated out from the total monthly energy bill where possible. This can
be accomplished by estimating monthly energy use for the other systems-such as lighting,
electric power, and domestic water heating-that are not weather-dependent. Subtracting
this energy use from the overall monthly usage yields energy use related to HVAC.
This value should then be normalized
by dividing by the number of heating or cooling degree-days during that month, then
graphing the data. This type of monitoring and tracking provides for early recognition of
high energy use, malfunctioning equipment, or the need for maintenance.
As described in the February 1996
Training Series on energy accounting and economic analysis, an annual energy index for
each building or facility can be developed and compared with similar buildings within the
same geographical or climate region. This annual index should cover all fuels and should
be in units of thousand Btu's per square foot of floor space per year.
There are general ranges for energy
usage based on type of occupancy classification, as shown in Table 1. These values are
very general, but they tend to illustrate the varying energy usage among building
classifications. The large range shown within each building type is the result of
differences in buildings, usage, and weather. While these ranges are broad, they still
permit a comparison to be made to see where a particular building fits in the range. When
the annual energy use of a building is in the upper half of the range, there is probably
an opportunity to save energy dollars by applying energy management strategies.
Improving
the energy efficiency of an HVAC system is a continuous operation. In general, 10-30
percent of the energy usage can be saved in systems just by implementing good maintenance
practices. What makes energy efficiency difficult is that there are many components in an
HVAC system that require annual inspection and maintenance. Savings from any one component
may be small, but when all the individual components are added together the savings can be
substantial. Remember, energy conservation is not necessarily the goal. Rather, the goal
is to use only the energy needed and to use that energy as efficiently as possible. |
Charles Fafard is
vice-president of engineering for Resource Management Associates, an international
consulting services firm based in Madison, Wis. RMA provides specialized professional
consulting and applied research services with the goal of promoting the sustainable use of
energy resources. Clients include U.S. DOE, USAID, World Bank, Asian Development Bank,
OECD, the government of Thailand, the Czech Ministry of Environment, the Energy Center of
Wisconsin, and the State of Wisconsin.
|